PROline Prosonic Flow 93 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 109
Example 2:
Replacing measured variables with placeholders (EMPTY_MODULE) using the
manufacturer-specific GSD file:
This form of configuration activates the volume flow channel 1, totalizer 2 “without
control”, totalizer 3 with control, display value and the manufacturer-specific control
block. In this example, totalizer 2 “without control” only provides the measured value
and thus cannot be controlled. It is not possible to reset or stop totalizer 2.
F06-93PBxxxx-20-xx-xx-xx-002
Slot 1: AI volume flow CH1
Slot 2-9: Place holder (EMPTY_MODULE)
Slot 10: Totalizer 2 “without control“
Slot 11: Totalizer 3 + control (SETTOT_MODETOT_TOTAL)
Slot 12: Display value (DISPLAY_VALUE)
Slot 13: Control (CONTROL_BLOCK), manufacturer-specific
Configuration data
Byte length
(Input)
Byte length
(Output)
Data blocks Status Access type GSD
Block designation
GSD
Extended block
identification
GSD
Standard block
identification
0...4 – Volume flow CH1
+ Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
– – Placeholder inactive – EMPTY_MODULE 0x00 0x00
5...9 – Totalizer 2 + status active read TOTAL 0x41, 0x84,
0x85
0x41, 0x84,
0x85
10...14 0 + 1 Totalizer 3 + status
+ control
active read + write SETTOT_MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
– 2...6 Display value active write DISPLAY_VALUE 0x82, 0x84,
0x08, 0x05
0xA4
– 7 Control variable active write CONTROL_BLOCK 0x20 0x20