6 Commissioning PROline Prosonic Flow 93 PROFIBUS-DP/-PA
110 Endress+Hauser
Example 3:
Configuration of the measured variables without placeholders (EMPTY_MODULE) using
the manufacturer-specific GSD file.
This configuration transmits the volume flow channel 1 and the sound velocity
channel 1.
!
Note!
If no further measured variables are required, the placeholders will not have to be used.
This only applies if no manufacturer-specific controls are used.
F06-93PBxxxx-20-xx-xx-xx-003
Slot 1: AI volume flow CH1
Slot 2: AI sound velocity CH1
Configuration data
Byte length
(Input)
Byte length
(Output)
Data blocks Status Access type GSD
Block designation
GSD
Extended block
identification
GSD
Standard block
identification
0...4 – Volume flow CH1
+ Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 – Sound velocity
CH1 + status
active read AI 0x42, 0x84,
0x08, 0x05
0x94