6 Commissioning PROline Prosonic Flow 93 PROFIBUS-DP/-PA
110 Endress+Hauser
Example 3:
Configuration of the measured variables without placeholders (EMPTY_MODULE) using
the manufacturer-specific GSD file.
This configuration transmits the volume flow channel 1 and the sound velocity
channel 1.
!
Note!
If no further measured variables are required, the placeholders will not have to be used.
This only applies if no manufacturer-specific controls are used.
F06-93PBxxxx-20-xx-xx-xx-003
Slot 1: AI volume flow CH1
Slot 2: AI sound velocity CH1
Configuration data
Byte length
(Input)
Byte length
(Output)
Data blocks Status Access type GSD
Block designation
GSD
Extended block
identification
GSD
Standard block
identification
0...4 Volume flow CH1
+ Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 Sound velocity
CH1 + status
active read AI 0x42, 0x84,
0x08, 0x05
0x94