PROline Prosonic Flow 93 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 111
Example 4:
Full configuration using the Profile GSD files PA039741.gsd (RS 485) and
PA139741.gsd (IEC 61158-2 (MBP))
This configuration transmits the volume flow channel 1, the sound velocity channel 1
and the totalizer 1 + control.
!
Note!
There is no difference between the block ID's of the two Profile GSD files PA039741.gsd
(RS 485) and PA139741.gsd (IEC 61158-2 (MBP)).
There is, however, a difference in the baud rates that are supported and the
Min_Slave_Interval.
F06-93PBxxxx-20-xx-xx-xx-004
Slot 0: AI volume flow CH1
Slot 1: AI sound velocity CH1
Slot 2: Totalizer 1 + control
(SETTOT_MODETOT_TOTAL)
Configuration data
Byte length
(Input)
Byte length
(Output)
Data blocks Status Access type GSD
Block designation
GSD
Extended block
identification
GSD
Standard block
identification
0..4 Volume flow CH1 +
status
active read AI 0x94
5...9 Sound velocity CH1
+ status
active read AI 0x94
10...14 0...1 Totalizer 1 + status
+ control
active read +
write
SETTOT_MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85