EasyManua.ls Logo

Festo SOPA - Setting the Switching Characteristics of the Binary Signals (EDIT Mode)

Festo SOPA
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Some menu options or setting values are not applicable depending on the product variant and the
selected switching function.
Legend Meaning
Edit button
A or B pushbutton
Bold Factory setting
1) Menu column only for PNLK-VB/A
2) Menu item only with PNLK-VB
3) Menu item only for PNLK-VB/A
4) Menu column and menu item only for 2P/2N
Tab. 18 Legend for menu structure EDIT mode
8.3 Setting the switching characteristics of the binary signals (EDIT mode)
The distance monitoring function can be set for the binary signals OutA and OutB.
The supply pressure monitoring function can be set for binary signal OutC
è 5.2.2.1 Switching signals.
Setting distance monitoring for OutA
The procedure for setting the distance monitoring for OutA and OutB is basically identical. The proced-
ure is described below based on the binary signal OutA.
Requirement: EDIT mode is active.
1. Select [OutA] with the A or B pushbutton.
2. Press the Edit button to confirm the selection.
Ä
[SP] flashes.
3. Set switching point with the A or B pushbutton.
4. Press the Edit button to confirm the set value.
Ä
[HY] flashes.
5. Set value for hysteresis with A or B pushbutton.
6. Press the Edit button to confirm the set value.
Ä
[NO] or [NC] flashes.
7. Select the switching element function with the A or B pushbutton.
8. Press the Edit button to confirm the selection.
Ä
RUN mode is active.
9. Use a test run to check that the sensor switches as desired (switching point and hysteresis).
Commissioning
28 Festo — SOPA — 2020-04

Table of Contents

Other manuals for Festo SOPA

Related product manuals