Option Meaning
1 Spurious pulse suppression when using the measuring air on/off function with
deactivated exhaust air
2 Spurious pulse suppression with use of the exhaust air on/off function and with
measuring air continuously on
Tab. 19 Options for spurious pulse suppression
8.8 Switch off display (EDIT mode)
The numerical display (7-segments) for the distance-correlated value and the backlighting of the dis-
play can be switched off permanently or with an adjustable delay time. Both settings allow time-lim-
ited use of the INFO mode and the SHOW mode.
Switch off 7-segment display/backlighting
Requirement: EDIT mode is active.
1. Select the Special menu [Spec] with the A or B pushbutton.
Ä
[Spec] flashes.
2. Press the Edit button repeatedly until [di.] flashes.
3. Select parameter with A or B pushbutton.
[di.OF]: 7-segment display is off.
[di.ON]: 7-segment display is permanently on.
[di.1]…[di.90]: 7-segment display switches off automatically after the set duration (in
minutes).
[di.EC]: backlighting of the display switches off automatically after 60seconds.
4. Press the Edit button to confirm the set value.
Ä
The next adjustable parameter is shown.
8.9 Changeover of binary output OutA (EDIT mode)
Requirement: EDIT mode is active.
1. Select the Special menu [Spec] with the A or B pushbutton.
Ä
[Spec] flashes.
2. Press the Edit button repeatedly until [PnP] or [nPn] flashes.
3. Select function of the binary output with A or B pushbutton.
4. Press the Edit button to confirm the set value.
Ä
The next adjustable parameter is shown.
8.10 Setting the allocation of the switching output at Pin 2 (EDIT mode)
Requirement: EDIT mode is active.
1. Select the Special menu [Spec] with the A or B pushbutton.
Ä
[Spec] flashes.
2. Press the Edit button repeatedly until [P2-] flashes.
3. Select parameter with A or B pushbutton.
b = OutB = additional switching point for distance monitoring
c = OutC = supply pressure monitoring
Commissioning