Annex
FLUXUS WD A Menu structure
163
UMFLUXUS_WDV1-3EN, 2018-07-16
Example 1
The diagnostic values are to be checked.
If the SCNR is < 20 dB, a snap has to be triggered.
trigger:
condition:
action:
SCNR 20 dB
R1 with SCNR < 20 dB
trigger a snap
Options Special functions
Channel A Snap
Event trigger
Configuration
Select R1 On
Enable R1 Snap ringbuffer
Yes Yes
Source item Auto snap
Diagnostic
values
No
Diagnostic
values
SCNR Snap on R1
Function Yes
MIN (x<limit)
Type
Non-hold
Trigger value
20.0 dB
Hysteresis
1.0 dB
Glitch interval
1.0 s
Failure delay
1.0 s