EasyManuals Logo

Flowserve MX User Manual

Flowserve MX
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
Limitorque
®
MX Electronic Actuator FCD LMENIM2306-09-AQ – 08/17
26
Particular care should be taken when terminating twisted-pair shielded cables in a control network. Avoid nicks, cuts, or
abrasions in the insulation of data communication cables, since this may result in inadvertent ground connection. Also,
excess cable should be cut, not coiled or looped, to prevent noise induction into the network.
Limitorque strongly recommends remote communication wiring be routed separately from mains line power wiring.
Specifically, instrumentation wiring, including communication, analog and discrete signal wiring, should be routed
in conduit that is separated from power lines. If the recommendation is not followed, the intergrity of instrumenta-
tion signals may be comprimised. If the signal is comprimised, the MX will enter a“safe-state” whereby all motion is
prohibited until communication is sucessfully re-established.
Figure 3.13 – View of terminal block
Figure 3.14 – Standard wiring diagram illustrating 3 phase motor voltage applied.
NOTE: Most current wiring diagram is shipped within the terminal compartment of the MX.
Cable Preparation
Prepare the network cable for connection to the MX actuator terminal block as illustrated in Figures 3.15 through 3.18.
a
CAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the conductor.
Do not nick conductors when stripping away the insulation. Nicking stresses the conductor and can cause the
conductor to break. This type of damage may not be apparent and failure can occur later without warning.
Grounding lug
View of terminal block
Reversing
contactor
Close
Stop
Open
Dig Com #1-Ve
Close inhibit/
interlock Input 1
interlock Input 2
Open inhibit/
Dig Com #2-Ve
0 VAC
110 VAC
24 VDC +Ve
0 VDC
24 VDC +Ve
0 VDC
27
26
25
35
28
29
34
24
23
21
22
7
6
L1
L2
L3
FS1 FS2
FS3
LimiGard
Motor
board
Power
PE
Three-phase supply
Control
supply
Aux.
input
(Optional)
*
E.S.D. Input 0
Dig Com #3-Ve
32
30
Position
sensor
44
45
48
49
46
47
50
51
S1a
S1b
S2a
S2b
CLOSE
position
OPEN
position
54
53
52
Show n
with
power
supply off
Control panel
Torque
sensor
Monitor relay
Circuit shown with valve in fully
closed position and with power off.
Main processor board
Status feedback
output switches
Default setting
CLOSE
position
OPEN
position
CLOSE
STOP
OPEN
(YES)
REMOTE
LOCAL
(NO)
Limitorque
*
Jumpers may be added to connect digital commons - pt. 28 & 29, 31& 32
Note: 110 VAC control supply from actuator is optional.
LMENIM2306-09 AQ.indd 26 Mittwoch23.08.17 08:53

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flowserve MX and is the answer not in the manual?

Flowserve MX Specifications

General IconGeneral
BrandFlowserve
ModelMX
CategoryController
LanguageEnglish

Related product manuals