Limitorque
®
MX Electronic Actuator FCD LMENIM2306-09-AQ – 08/17
90
“---% OPEN, THERMISTOR” – There is a failure with the motor thermistor
“---% OPEN, KNOBS” – There is a failure with the local knobs
“---% OPEN, DDC NOT PRESENT” – DDC board expected but not found (missing or not communicating)
“---% OPEN, FF NOT PRESENT” – FF board expected but not found
“---% OPEN, PBDP NOT PRESENT” – Profibus DP board expected but not found
“---% OPEN, PBPA NOT PRESENT” – Profibus PA board expected but not found
“---% OPEN, DN NOT PRESENT” – Device Net board expected but not found
“---% OPEN, ANG1 NOT PRESENT” – Analog 1 board expected but not found
“---% OPEN, ANG2 NOT PRESENT” – Analog 2 board expected but not found
“---% OPEN, CONTACTOR” – Contactor failure
“---% OPEN, ENCODER” – Encoder failure
“---% OPEN, R1R4RM RLY FAILED” – R1-R4 board relay check failed
“---% OPEN, R5R8 RLY FAILED” – R5-R8 board relay check failed
“---% OPEN, DDC FAILED” – Communication with the main board failed, or hardware fault
“---% OPEN, FF FAILED” – Communication with the main board failed, or hardware fault
“---% OPEN, PBDP FAILED” – Communication with the main board failed, or hardware fault
“---% OPEN, PBPA FAILED” – Communication with the main board failed, or hardware fault
“---% OPEN, DN FAILED” – Communication with the main board failed, or hardware fault
“---% OPEN, R1R4RM NOT AVAIL” – R1-R4 board expected but not found
“---% OPEN, R5R8 NOT PRESENT” – R5-R8 board expected but not found
“---% OPEN, ENCODER WARNING” – The encoder has not yet failed, but there was a momentary glitch detected.
If the glitch persists, encoder failure will be reported.
“---% OPEN, FF COM Lost” – FF enabled, signal absent
“---% OPEN, PB COM Lost” – PB enabled, signal absent
“---% OPEN, DN COM Lost” – DN enabled, signal absent
---%OPEN, ESD XX ACTIVE – Input # set for ESD, is asserted, and has highest priority
---%OPEN, ESD = XXX.X % = ESD ACTIVE and its action is “move to” ---.-% position
---%OPEN, ESD XX INHIBITED – Active ESD XX has been inhibited by an ESD override
---%OPEN, ESD XX CONFLICT – ESD XX is set for ESD, asserted, and is in conflict with the active ESD
---%OPEN, ESD OPEN – active ESD action is OPEN
---%OPEN, ESD CLOSED – active ESD action is CLOSED
---%OPEN, ESD STOP – active ESD action is STOP
---%OPEN, ESD IGNORE – active ESD action is IGNORE
--%OPEN, INHIBIT ACTIVE – INHIBIT signal is asserted
LMENIM2306-09 AQ.indd 90 Mittwoch23.08.17 08:53

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flowserve MX and is the answer not in the manual?

Flowserve MX Specifications

General IconGeneral
BrandFlowserve
ModelMX
CategoryController
LanguageEnglish

Related product manuals