NOTE 
This  section  conm'm progrCUnrnLCUnmLng instruc- 
tions for use with the IEEE-488 Interface 
(Op- 
tion 
-05). 
For insraUafion instructions, refer 
to 
the  Options 
and 
Accessories  section 
3-1. 
INTRODUCTION 
The  IEEE-488  Interface 
turns 
the  8$4OA  into  a  fully 
programmable instrument for use with  the IEEE Standard 
488-1978  interface  bus  (IEEE-488  bus).  With  the 
IEEE-488  Interface,  the 
8840A can  become 
part 
of  an 
automated  instrumentation  system.  The 
8840A 
can 
be 
under  complete,  interactive  control 
from 
a  remote  bus 
controller; or 
it 
can 
be 
set to the talk-only mode, co~e~ted 
to a data logger or printer, and dedicated to a single 
task. 
This  manual  assumes  you  know  the  basics  of  the 
IEEE-488 interface bus.  For  an  introduction to the bus, 
request Fluke Application Bulletin 
AB-36, 
"IEEE  Standard 
488-1978 Digital Interface for Programmable Insmmenta- 
tion." 
3-2. 
CAPABILITIES 
The  IEEE-488  Interface  provides  remote  control  of  all 
front  panel  controls  except  for  the 
POWER, 
CAL 
ENABLE,  and  FRONTIREAR  switches.  Other  features 
include: 
A  simple and  predictable command set 
Fast  measurement  throughput 
Full  talWlisten  capability, including  talk-only  opera- 
tion 
Full  serial  poll  capability, with  bit-maskable  SRQ 
Full  remote/locai capability, including local  lockout 
Section 
3 
Remote 
Programmihg 
I 
EXTERNAL  TRIGGER  and  SAMPLE 
COMP&ETE 
connectors 
Remote calibration 
Programmable trigger sources, including two bw4  trig- 
gers 
I 
Informative  output  suffix (suppressible) 
Selectable output  terminators 
The 8840A supports the following interface function sub- 
sets: SHl, 
AH1, 
T5, 
L1, 
SR1, RL1,  DCl, DT1, 
~1,; 
PPO, 
and  CO. 
, 
3-3. 
BUS 
SET-UP 
PROCEDURE 
To set up  the 
8840A 
on  the IEEE-488  bus,  proc* 
as 
follows: 
1. 
Turn  the  8840A  POWER  switch  OFF  and 
s+ 
the 
8840A  IEEE-488  address  using  the  rear  banel 
IEEE-488 address switches shown  in  Figure 
3-1. 
2. 
With  the  8840A  POWER  switch 
OFF, 
plug  the 
IEEE-488 cable into the 8840A rear panel IEE~-488 
connector. 
3. 
Switch on  the  8840A. 
Whenever the  8840A is in  the local  state, the IEEP-488 
address 
can 
be 
displayed on the front panel 
by 
pressi4g the 
LOCAL button. 
An 
overview of  remote operation is presented in the block 
diagram  in  Figure 
3-2. 
Each  block  represents a re  'ster, 
B 
buffer, etc.,  contained in the 8840A. The status regi  ers in 
the center column indicate the instrument's  status, iiclud- 
ing its function, range, reading rate, etc.  The input buffer 
receives data  from  the  IEEE-488  bus.  The output  pffer 
receives 
data 
from the blocks to its left, 
and 
sends d&ta on 
to  the IEEE-488 bus. 
3- 
1 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com