Remote  Programming 
AN 
OVERVIEW 
OF 
REMOTE 
OPERATION 
Information  is  transferred  between  blocks  by  device- 
36. 
DEVICE-DEPENDENT COMMAND 
SET 
- 
dependent commands. 
bCh 
command is shown next to an 
Devi=&pen&nt  commands 
are 
the  hem  of 
arrowhead which indicates the resulting information trans- 
remote  conBol.  They  tell  the 
the input buffer and stores it in the 
primary 
status 
registers.  make se~ce requests, etc. Cdmmands which  cor 
fer. For  example,  Put  command 
PO 
takes a number  from 
make measurements, when to put data on the bus, whkn to 
Likewise,  Get  command 
GO 
gets the  content of the 
pri- 
directly to the 
front 
panel conthls or 
display 
are 
mary 
status 
registers and copies it into the output buffer. 
Figure  34. The complete 
set 
of device-depenht 
man&  is  listed  in  Figure 
3-5. 
The 
3-5. 
A 
NOTE 
ABOUT 
EXAMPLES 
entered using either upper- or lower-case letters. 
See 
table 
6-15 for conditions under whiuh certain cornman&  de not 
In  the examples in  this  manual,  device-dependent 
com- 
vdid. 
marids are shown enclosed within quotation 
marks, 
as they 
would 
be 
entered 
in 
Fluke BASIC.  For  clarity, the com- 
Devicedependent commands  are  &.vice-&pendent  me- 
mads 
are 
also 
separated by 
spaces. 
Hmever, the 
SPm 
sages. 
For the 
884OA 
to receive them,  they  must 
be/ 
sent 
are  are not  necessary  and may 
be 
omitted. 
over the IEEE-488 bus  when the 
884OA 
is 
in 
remote and 
has 
been 
addressed 
as 
a 
listmer. 
Example  Explanation 
I 
I 
ONLY  ONLY  ONLY 
"* 
F3 R1 S1 
T2" 
This  example  is  equivalent  to 
"*F3RlSl'I2"  or  "*,F3,Rl,Sl,V"' 
?) 
are  described last. 
00 
01 
02 
03 
04 
05 
06 
07 
08 
09 
10 
Using the Fluke 172214 hstrurnent Controller, these com- 
3-7. 
Bn 
(offset 
Commands) 
I 
be 
vniltra 
into 
a 
pro@= 
as 
shown 
me 
Offset man& dupli~te the fundon of the 
front 
in 
Figure 3-3. Examples using other controllers are given 
omsFT 
buaon. 
when 
the 
MA 
rccdva 
de 
~1 
at  the end of  this  section. 
command,  the 
WA 
stores the  present  reading 
bs 
an 
offset  for the present function. The BO  command 
8840A 
Output 
data 
show 
the 
terminators 
CR 
the offset. 
As 
with 
front panelloperaion, only one 
and 
LF. 
The terminator EOI  is not shown 
because 
it 
is 
a 
allowed 
at 
a 
time. 
uniline  message.  However,  the terminators 
CR, 
LF, 
and 
EOI 
are  all  selectable using the  Write  commands. 
The offset status (not the offget value) 
can 
be 
the 
G5 
command.  The  8840A  defaults to 
For  reference,  the  ASCII  and  IEEE  Std  488-1978  bus 
power-up 
and 
on any  device-clear command 
(*, 
codes are shown  at  the  back  of  this section.  SDC). 
I 
I 
Fiure 
3-1. 
IEEE-488 
Address 
Selection 
000000 
000001 
000010 
000011 
000100 
000101 
000110 
000111 
001000 
001001 
001010 
11 
12 
13 
14 
15 
16 
17 
18 
19 
-20 
21 
001011 
001100 
001101 
001110 
001111 
010000 
010001 
010010 
010011 
010100 
0 1 
0 
1 0 1 
22 
23 
24 
25 
26 
27 
28 
29 
30 
31 
TALK 
ONLY 
0 10 1lIO 
0 10 1 
lll 
0 11 0 010 
0 11 0 011 
0 11 0 
lIO 
0 11 0 111 
01 11 010 
0 11 1 
O+ 
0 11 1110 
Not 
allowed 
1 
X 
X 
X 
XIX 
XI 
I 
= 
setting does not 
matter, 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com