114
Setting the
pressure unit
The pressure unit can be shown in MPa or PSI.
IMPORTANT! Factory set item is MPa.
Setting the pressure unit:
1. Press the button MENU for 2 seconds.
► Monitoring menu appears.
2. Press the button MENU again for 2 seconds.
► Setting level SE.01 (Activating key-lock) is shown.
4. Use the ARROW buttons to make the required setting:
Display shows [mPA]: Pressure unit is MPa
Display shows [PSI]: Pressure unit is PSI
5. Press the MENU button again.
► The entered setting will be saved.
3. Press the button SEL for12 times.
► Setting level SE.13 is shown.
Data reset
function
Carry out a data reset:
1. Press the button MENU for 2 seconds.
► Monitoring menu appears.
2. Press the button MENU again for 2 seconds.
► Setting level SE.01 (Activating key-lock) is shown.
4. Use the ARROW buttons to make the required setting:
Dispplay shows [no]: No data reset (default setting).
Display shows [yes]: All data is reset.
5. Press the MENU button again.
► The entered setting will be saved.
3. Press the button SEL for 13 times.
► Setting level SE.14 is shown.
With this function, all the values set by the customer are reset to factory default settings.
Exception: Total operating time of the water chiller will not be reset.