89
Technical data
Rating plate
Rating plate CU 1800
Cooling capacity (50 Hz / 60 Hz)
(1)
1800 W / 2100 W
Temperature range setting 5 - 40° C
Ambient temperature / humidity
Temperature: 5 up to 40 °C, Humidity: 30 up
to 70 %
Temperature stability +/- 0,1° C
Pump capacity (50 / 60 Hz)
0,44 MPa (bei 10 l / min) /
0,40 MPa (bei 14/min)
Rated ow (50 / 60 Hz) 10 l /14l / min
Tank capacity ca. 5 l
Cooling liquid
Fronius FCL 10, Art.-Nr.: 40,0009,0180 (5l) /
40,0009,0181 (30l)
Refrigerant R407C (HFC)
Refrigerant capacity
0,36 kg
Max. / Min.: 2,0 / 0,6 MPa
Mains voltage
200 - 230 V AC (50 - 60 Hz)
Allowable voltage range +/- 10 %
Rated operating current (50 Hz / 60 Hz) 5,1 / 5,9 A
Rated power consumption
(50 Hz / 60 Hz)
1,0 / 1,2 kVA
Circuit protector 10 A
(1)
Cooling liquid: clear water, cooling liquid temperature: 20° C,
ambient-/ facility water temperature: 25°C
Noise level
When used according to its intended purpose, the water chiller generates a maximum
sound power level of 60 / 61 dB (50 Hz / 60 Hz), (ref. 1pW) as measured according to
EN ISO 11201.
NOTE! The rating plate may not be removed or modied without the consent
of Fronius International GmbH. Ensure that the rating plates remain legible.
XXXXXXXX
8,045,635
CU 1800 Chiller
weight
44,5 kg377 x 735 x 615 mm
L x W x H
0,3 kA
AIC
0,36 kg p
H/L
GWP: 1774 2 / 0,6 MPa
1~
50 / 60 Hz
I1
5,1 / 5,9 A
U
1±10 %
200-230 VAC
Refrigerant
R407C (HFC)
10 A
Ser.No.:
Art.No.:
www.fronius.com
Froniusstraße 1
Pettenbach 4643