Fronius Symo Advanced 15.0-3-M
Current (inrush)
5)
27.2 A peak /
5.18 A rms over 5.4 ms
4)
Power factor (cos phi)
0–1 ind./cap.
2)
Maximum output fault current / duration 64 A / 2.34 ms
General data
Maximum efficiency 98%
European efficiency U
DCmin
/ U
DCnom
/
U
DCmax
96.2 / 97.6 / 97.1%
Self-consumption at night 0.7 W & 117 VA
Cooling Controlled forced-air
ventilation
Protection class IP 66
Dimensions h x w x d 725 x 510 x 225 mm
Weight 43.4 kg / 43.2 kg
Permitted ambient temperature -25 °C - +60 °C
Permissible humidity 0-100%
EMC emission class B
DC / AC overvoltage category 2 / 3
Pollution degree 2
Noise emission 65 dB(A) (ref. 1pW)
Inverter topology Non-insulated trans-
formerless
Protection devices
DC isolation measurement Integrated
DC overload performance Operating point shift,
power limiter
DC disconnector Integrated
RCMU Integrated
Active anti-islanding method Frequency conversion
method
AFCI - Arc Fault Circuit Interrupter (Arc Guard) Integrated
AFPE (AFCI) classification (according to
IEC63027)
F-I-AFPE-1-6-1
Full coverage
Integrated
AFPE
1 monitored string per in-
put port
6 input ports per channel
(AFPE for MPP1 & MPP2:
6)
1 monitored channel