Fronius Symo Advanced 10.0-3-M - Settings if the DC SPD Option Is Installed

Fronius Symo Advanced 10.0-3-M
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USB log book
Activates or deactivates the function for saving all error messages to a USB
flash drive AUTO / OFF / ON
-
ON: All error messages are automatically saved to a connected USB flash
drive.
Input signal
-
How it works: Ext Sig. / S0-Meter / OFF
operating mode Ext Sig.:
-
Triggering method: Warning (warning shown on display) / Ext. Stop
(inverter switches off)
-
Connection type: N/C (normally closed contact) / N/O (normally open
contact)
S0 meter operating mode – see chapter Dynamic power reduction by
means of inverter on page 23.
-
Grid feed-in limit
Field for entering the maximum grid feed-in power in W. If this value
is exceeded, the inverter regulates down to the set value within the
time required by national standards and regulations.
-
Pulses per kWh
Field for entering the pulses per kWh of the S0 meter.
SMS / relay
-
Event delay:
for entering the time delay after which an SMS is sent or the relay is to
switch
900–86,400 seconds
-
Event counter:
for entering the number of events that lead to signalling:
10 - 255
Isolation setting
-
Isolation warning: ON / OFF
-
Threshold warning: for entering a threshold that leads to a warning
-
Threshold fault: for entering a threshold that leads to a fault (not avail-
able in all countries)
TOTAL Reset
Under the LOG menu item, this setting resets the max. and min. voltage values
and the max. power of feeding in to zero.Once the values have been reset, this
action cannot be undone.
To reset the values to zero, press the "Enter" key.
"CONFIRM" is displayed.Press "Enter" again.
The values are reset and the menu is displayed
Settings if the
"DC SPD" option
is installed
If the option: DC SPD (surge protection) has been fitted in the inverter, the fol-
lowing menu items will be set by default:
Signal input: Ext Sig.
Triggering method: Warning
Connection type: N/C
97