Alarm function:
ALL / Per-
manent:
Switching the floating switch contact for permanent and tem-
porary service codes (e.g. brief interruption to energy being
fed into the grid, a service code occurs a certain number of
times a day - can be adjusted in the "BASIC" menu)
GAF As soon as GAF mode is selected, the relay is switched on.
The relay opens as soon as the power stage set registers an
error and goes from normally feeding energy into the grid to
being in an error state. This means that the relay can be used
for fail-safe functions.
Application example
It may be necessary to perform phase compensation when us-
ing a single-phase inverter at a multiphase site. If an error oc-
curs on one or several inverters and the connection to the grid
is broken, the other inverters must also be disconnected to
maintain the phase balance. The "GAF" relay function can be
used in conjunction with the Datamanager or an external pro-
tection device to recognise or signal that an inverter is not
feeding in or is disconnected from the grid and to then dis-
connect the remaining inverters from the grid using a telecon-
trol command.
Active output:
ON: The floating NO contact is on all the time the inverter is in op-
eration (as long as the display is not dark or is displaying
something).
OFF: The floating NO contact is off.
Energy Manager:
E-Manager: Further details on the "Energy Manager" function may be
found in the "Energy Manager" section.
Relay test
Function test to determine whether the floating switch contact switches
Switch-on point (only if "Energy Manager" function is activated)
for setting the effective power limit beyond which the floating switch contact is
switched on
Factory setting 1000 W
Setting range Set switch-off point up to the maximum nominal output
of the inverter (W or kW)
Switch-off point (only if "Energy Manager" function is activated)
for setting the effective power limit beyond which the floating switch contact is
switched off
Factory setting 500
Setting range 0 to the set switch-on point of the inverter (W or kW)
Energy Manager
(under Relay
menu item)
The "Energy Manager" (E-Manager) function can be used to activate the floating
switch contact in such a way that it functions as an actuator.
Thus, a consumer that is connected to the floating switch contact can be con-
trolled by specifying a switch-on or switch-off point that depends on the feed-in
power (effective power).
82

Table of Contents

Other manuals for Fronius Symo Advanced 10.0-3-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Symo Advanced 10.0-3-M and is the answer not in the manual?

Fronius Symo Advanced 10.0-3-M Specifications

General IconGeneral
AC nominal output10.0 kW
Max. efficiency98.1%
MPPT voltage range200 - 800 V
Number of MPPT2
Protection classIP66
Max. output current14.5 A
THD< 3%
Max. input voltage1000 V
Operating temperature range-25°C - +60°C
Max. apparent AC power10 kVA
AC nominal voltage400 V
Power factor (cos φac,r)1
DC max. power15, 000 W
Warranty5 years
CoolingFan