Data communication
Permitted cables
for the data
communication
area
max. 30 m
Unshielded
max. 3 m
Unshielded
max. 30 m
Shielded
max. 30 m
Unshielded
max. 30 m
Unshielded
max. 300 m
Shielded
S0 USB IOs
Solar Net
LAN
Relay
Routing data
communication
cables
IMPORTANT! Operating the inverter with one option card and two broken-out
option card slots is not permitted.
To cater for this eventuality, a suitable blanking cover (item number
42,0405,2094) is available from Fronius as an option.
IMPORTANT! If data communication cables are wired into the inverter, observe
the following points:
-
Depending on the number and cross-section of the data communication
cables that are being introduced, take the relevant blanking plugs out of the
sealing insert and insert the data communication cables.
-
The relevant blanking plugs must be inserted into the free openings on the
sealing insert.
1 2
58

Table of Contents

Other manuals for Fronius Symo Advanced 10.0-3-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Symo Advanced 10.0-3-M and is the answer not in the manual?

Fronius Symo Advanced 10.0-3-M Specifications

General IconGeneral
AC nominal output10.0 kW
Max. efficiency98.1%
MPPT voltage range200 - 800 V
Number of MPPT2
Protection classIP66
Max. output current14.5 A
THD< 3%
Max. input voltage1000 V
Operating temperature range-25°C - +60°C
Max. apparent AC power10 kVA
AC nominal voltage400 V
Power factor (cos φac,r)1
DC max. power15, 000 W
Warranty5 years
CoolingFan