Menu items in the Set-up menu
Standby Manual activation / deactivation of Standby mode
-
No energy is fed into the grid.
-
The Startup LED will show steady orange.
-
In the display, STANDBY / ENTER are alternately displayed
-
In Standby mode, no other menu item at menu level can be accessed or ad-
justed.
-
The automatic switchover into the "NOW" display mode after 2 minutes of
keyboard inactivity does not occur.
-
Standby mode can only be terminated manually by pressing the "Enter" key.
-
Pressing "Enter" at any time will cause energy to resume feeding into the
grid, as long as there is no error (state code)
Switching off Standby mode (manually switching off feeding energy into the
grid):
1
Select the "Standby" item
2
Press "Enter" function key
"STANDBY" and "ENTER" appear alternately on the display.
Standby mode is now active.
The Startup LED shows steady orange.
Resuming feeding energy into the grid:
In standby mode, the display alternates between 'STANDBY' and 'ENTER'.
1
Press the "Enter" function key to resume feeding energy into the grid
The "Standby" menu item is displayed.
At the same time, the inverter enters the startup phase.
The operating state LED shows steady green when feeding energy into the grid
has been resumed.
DATCOM Checking data communications, entering the inverter number, protocol settings
Setting range Status / inverter number / protocol type
Status
Indicates data communication is taking place via Fronius Solar Net or that a
data communications error has occurred
Inverter number
Sets the number (= address) of the inverter in a system with several inverters
Setting range 00 - 99 (00 = inverter address 100)
Factory setting 01
IMPORTANT! If a number of inverters are linked together in a data communic-
ations system, assign a unique address to each one.
Protocol type
Specifies the communications protocol to be used to transfer the data:
79