Country-specific
setting:
Setup - specified country setup
Version - version of country setup
Origin activated - indicates that the normal country-
specific setup is activated.
Alternat. activated - indicates that the alternative coun-
try-specific setup is activated (for Fronius Symo Hybrid
only)
Group - group for updating the inverter software
MPP Tracker: Tracker 1 - indicates the set tracking behaviour (MPP
AUTO / MPP USER / FIX)
Tracker 2 - indicates the set tracking behaviour (MPP
AUTO / MPP USER / FIX)
Grid monitoring: GMTi - Grid Monitoring Time - start-up time of the in-
verter in sec (seconds)
GMTr - Grid Monitoring Time reconnect - reconnection
time in sec (seconds) after a grid fault
ULL - U (voltage) Longtime Limit - voltage limit value in
V (volts) for the 10-minute average voltage value
LLTrip - Longtime Limit Trip - trip time for ULL monitor-
ing, how fast the inverter should switch off
Grid voltage limits
inner limit value:
UImax - upper inner grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the up-
per inner grid voltage limit value in cyl*
UMin - lower inner grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the
lower inner grid voltage limit value in cyl*
*cyl = grid periods (cycles); 1 cyl corresponds to 20 ms
at 50 Hz or 16.66 ms at 60 Hz
Grid voltage limits
outer limit value
UMax - upper outer grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the up-
per outer grid voltage limit value in cyl*
UMin - lower outer grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the
lower outer grid voltage limit value in cyl*
*cyl = grid periods (cycles); 1 cyl corresponds to 20 ms
at 50 Hz or 16.66 ms at 60 Hz
88