SET3 setting
Wireless remote controller custom code switch
This DIP switch sets the custom code of the wireless remote controller of an indoor unit.
If multiple indoor units are being installed in the same room, switch the custom codes of the
corresponding wireless remote controllers in order to prevent their signals from being mixed.
When switching the custom code of the wireless remote controller of an indoor unit, be sure to
also switch the code setting on the paired wireless remote controller side at the same time.
(
u
...Factory setting)
SET3-1 SET3-2 Custom code
u
OFF OFF Type A
ON OFF Type B
OFF ON Type C
ON ON Type D
1
3
2
How to switch the code on the wireless remote controller side
1) Press the MODE button for more than ve seconds to
start the code change.
2) Press the SET TEMP. (
p
) or (
q
) button to select the
desired code.
A
B
C
D
3) Press the MODE button again to end the code change.
SET3-3, SET3-4 setting prohibited
(
u
...Factory setting)
SET3-3 SET3-4
u
OFF OFF Fixed at OFF
ON ON Setting prohibited
- (07 - 85) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals