2. Specifications
2-1. Compact cassette type
Model name AUUA4TLAV2 AUUA7TLAV2 AUUA9TLAV2
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 4,000 7,500 9,500
kW 1.2 2.2 2.8
Heating
Btu/h 4,400 9,500 10,900
kW 1.3 2.8 3.2
Input power W 23 25
Fan
Airflow rate
HIGH
CFM (m
3
/h)
312 (530) 318 (540) 324 (550)
MED—HIGH
288/283*
1
(490/480
*
1
)
295 (500) 306 (520)
MED
265/253*
1
(450/430
*
1
)
271 (460) 283 (480)
MED—LOW
247/224*
1
(420/380
*
1
)
247 (420) 259 (440)
LOW
230/200*
1
(390/340
*
1
)
230 (390) 236 (400)
QUIET
206/177*
1
(350/300
*
1
)
206 (350) 206 (350)
Type × Q'ty Turbo × 1
Motor output W 54
Sound pressure level*
2
HIGH
dB (A)
34 34 35
MED—HIGH
32/31*
1
32 33
MED
30/29*
1
30 31
MED—LOW
28/26*
1
28 29
LOW
27/24*
1
27 27
QUIET
25/21*
1
25 25
Heat exchanger type
Length in (mm) 50-3/8 (1,280)
Fin pitch FPI 21
Rows × Stages 2 × 10
Face area
ft
2
(m
2
)
2.9 (0.27)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net
in (mm)
9-5/8 × 22-7/16 × 22-7/16 (245 × 570 × 570)
Gross 10-7/16 × 28-3/4 × 24-5/8 (265 × 730 × 625)
Weight
Net
lb (kg)
32 (14.5) 33 (15)
Gross 40 (18)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35)
Gas (Flare) Ø 3/8 (9.52)
Drain hose I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
Cassette grille
(Grid type: Option)
Model name UTG-CCGVG
Color
White
Approximate color of Munsell 9PB 9.1/0.2
Dimensions
(H × W × D)
Net
in (mm)
1-15/16 × 24-7/16 × 24-7/16 (50 × 620 × 620)
Gross 4-3/4 × 30-1/8 × 29-3/4 (120 × 765 × 755)
Weight
Net
lb (kg)
5 (2.3)
Gross 10 (4.5)
Cassette grille
(Standard type: Option)
Model name UTG-CCGV
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
1-15/16 × 27-9/16 × 27-9/16 (50 × 700 × 700)
Gross 4-3/4 × 30-1/8 × 29-3/4 (120 × 765 × 755)
Weight
Net
lb (kg)
6 (2.6)
Gross 10 (4.5)
NOTES:
•
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: This value is “Cooling operation/Heating operation”.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-1. Compact cassette type - (04-4) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS