1-5. Automatic address setting
The addresses of signal amplifiers and indoor units can be set automatically.
CAUTION
Mind the following items when performing automatic address setting.
The controller cannot be used.
Automatic address setting may take about 30 minutes.
Emergency stop signal is not accepted.
When setting both addresses of Signal amplifiers and indoor units automatically, be sure to al-
ways set the addresses of signal amplifiers first.
¢ C
omponents location
Components related to automatic address setting are located on the outdoor unit PCB.
Set the functions of an outdoor unit with the push buttons (SW107, SW108, and SW109) while ob-
serving the 7-segment LED lamps (LED105 and LED104) on the PCB.
LED101
(GREEN)
SW107 SW108 SW109
SW106 SW105
SW110
POWER
MODE
MODE
/EXIT
LED105 LED104
REF AD
SET1 SET2 SET3 SET4
LED102
(RED)
ERROR
SELECT ENTER
X 10 X 1
SET5
Outdoor unit PCB
LED lamp
7-segment LED lamp
Rotary switch
DIP switch
DIP switch*
Push button
*: For details, refer to "Terminal resistor setting
" on page 07-56.
1-5. Automatic address setting - (07-49) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS