1-5. Control device design limitation
Central control
Central controller
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
System controller UTY-APGXZ1 USB adapter 1/system
1,600
(4 VRF
networks)
400
(4 VRF
networks)
System controller
lite
UTY-ALGXZ1 USB adapter 1/system
400
(1 VRF
networks)
100
(1 VRF
networks)
Touch panel
controller
UTY-DTGYZ1
16/system
400
100
Central remote
controller
UTY-DCGY
UTY-DCGYZ1
100
Adaptor/Convertor
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
Network convertor
UTY-VTGX
UTY-VGGXZ1
100/system
Network convertor
for LonWorks*
1
UTY-VLGX 1/system
128*
2
100
BACnet gateway
UTY-VBGX 4/system
128*
2
100
UTY-ABGXZ1 USB adapter 1/system
1,600
(4 VRF
networks)
400
(4 VRF
networks)
Modbus convertor UTY-VMGX 9/system
128*
2
100
Thermostat
convertor
UTY-TTRX
16*
3
Signal amplifier UTY-VSGXZ1 40/system
Wireless LAN
adapter
UTY-TFSXZ2
*1: A maximum of 4 Network convertors for LonWorks can be connected to 1 BMS.
*2: Maximum controllable indoor unit number per one convertor. (For proper configuration, re-
fer to system diagram of each device.)
*3: Maximum connectable indoor unit number per one remote controller group.
Service and Maintenance
Necessary
device
Maximum units number
Connectable
units
Manageable
indoor units
Connectable
outdoor units
Service tool UTY-ASGXZ1
USB adapter 1/system
400 100
Web monitoring
tool
UTY-AMGXZ1
1,600
(4 VRF
networks)
400
(4 VRF
networks)
1-5. Control device design limitation - (05-12) - 1. Control system
CONTROL
SYSTEM
CONTROL
SYSTEM