3-2. External input
• Operation/Stop, Emergency stop, or Forced stop of the indoor unit can be set by using CNA01 or
CNA02 on the indoor unit PCB.
• Start/Stop mode, Emergency stop mode, or Forced stop mode can be selected with function set-
ting of the indoor unit.
• Forced thermostat off of the indoor unit can be set by using CNA03 or CNA04 on the indoor unit
PCB.
• A twisted pair cable 22 AWG (0.33 mm
2
) should be used. Maximum length of cable is 492 ft (150
m).
• Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
• When connecting the external input wire, do not route the wire closely to the power cable line.
¢ I
nput select
Use either one of Apply voltage terminal of Dry contact terminal according to the application. (Both
types of terminals cannot be used simultaneously.)
• CNA01, CNA03: Apply voltage terminal
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal (CNA01, CNA03).
1
2
1
2
3
+
+
-
-
-
Input device 1
Input device 2
Input device 3
*
1
*
2
*
2
*
3
*
2
DC power supply
12 to 24 V
Connected unit
PCB
CNA01
CNA03
Load
resistance
Load
resistance
Load
resistance
*
1
:
Make the power supply DC12 to 24 V. Select a power supply capacity with an ample sur-
plus for the connected load. Do not impress a voltage exceeding 24
V across pins 1-2,
and 1-3.
*
2
:
The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*
3
:
The polarity is “+” for pin 1, and “-” for pin 2 and 3. Connect correctly.
3-2. External input - (08-10) - 3. Indoor unit
EXTERNAL INPUT
AND OUTPUT