2-3. Cassette type
Model name AUUB18TLAV AUUB24TLAV
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 18,000 24,000
kW 5.3 7.0
Heating
Btu/h 20,000 27,000
kW 5.9 7.9
Input power W 39 46
Fan
Airflow rate
HIGH
CFM (m
3
/h)
677 (1,150) 753 (1,280)
MED 553 (940) 612 (1,040)
LOW 512 (870) 512 (870)
Type × Q'ty Turbo × 1
Motor output W 80
Sound pressure level*
HIGH
dB (A)
36 38
MED 30 33
LOW 29 29
Heat exchanger type
Length in (mm) 81-15/16 (2,082)
Fin pitch FPI 21
Rows × Stages 2 × 10
Face area
ft
2
(m
2
)
4.5 (0.42)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net
in (mm)
9-11/16 × 33-1/16 × 33-1/16 (246 × 840 × 840)
Gross 12-1/2 × 37-13/16 × 38-9/16 (318 × 960 × 980)
Weight
Net
lb (kg)
49 (22)
Gross 60 (27)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 3/8 (9.52)
Gas (Flare) Ø 5/8 (15.88)
Drain hose I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
Cassette grille
(Option)
Model name UTG-LCGV
Color WhiteApproximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
1-15/16 × 37-3/8 × 37-3/8 (50 × 950 × 950)
Gross 4-1/2 × 40-3/16 × 39-3/8 (115 × 1,020 × 1,000)
Weight
Net
lb (kg)
13 (5.5)
Gross 19 (8.5)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-3. Cassette type - (04-8) - 2. Specifications