Model name AUUB36TLAV2 AUUB48TLAV2
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 36,000 48,000
kW 10.6 14.1
Heating
Btu/h 40,000 54,000
kW 11.7 15.8
Input power W 61 116
Fan
Airflow rate
HIGH
CFM (m
3
/h)
954 (1,620) 1,202 (2,040)
MED—HIGH 884 (1,500) 1,060 (1,800)
MED 825 (1,400) 937 (1,590)
MED—LOW 789 (1,340) 848 (1,440)
LOW 754 (1,280) 766 (1,300)
QUIET 677 (1,150) 677 (1,150)
Type × Q'ty Turbo × 1
Motor output W 81
Sound pressure level*
HIGH
dB (A)
41 47
MED—HIGH 40 45
MED 38 42
MED—LOW 37 39
LOW 35 36
QUIET 33 33
Heat exchanger type
Length in (mm) 81-1/4 (2,064)
Fin pitch FPI 19
Rows × Stages 3 × 12
Face area
ft
2
(m
2
)
5.6 (0.52)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net
in (mm)
11-5/16 × 33-1/16 × 33-1/16 (288 × 840 × 840)
Gross 13-3/8 × 37-13/16 × 37-3/8 (340 × 960 × 950)
Weight
Net
lb (kg)
65 (29.5)
Gross 75 (34)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 3/8 (9.52)
Gas (Flare) Ø 5/8 (15.88)
Drain hose
VP25
I.D.: Ø
3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
Cassette grille
(Option)
Model name UTG-LCGVCW
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
2-1/16 × 37-3/8 × 37-3/8 (53 × 950 × 950)
Gross 4-5/16 × 39-3/8 × 39-3/4 (110 × 1,000 × 1,010)
Weight
Net
lb (kg)
13 (6.0)
Gross 22 (10)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-2. Circular flow cassette type - (04-7) - 2. Specifications
INDOOR
UNITS
INDOOR