1. System design
1-1. Refrigerant system
¢ Connectable unit within 1 refrigerant system
Outdoor unit
Unit Quantity
Outdoor unit 1 unit
Indoor unit
Outdoor unit Connectable indoor unit conditions
Ton Model name
Cooling
capacity
(Btu/h)
Cooling capacity range Connectable number
6 AOU72RLAVL 72,000
50 to 150%
of outdoor unit cooling
capacity
1 to 18 units
8 AOU96RLAVL 96,000 1 to 24 units
10 AOU120RLAVL 120,000 1 to 30 units
CAUTION
When all indoor units are operating at maximum capacity, individual indoor unit operates at a
slightly lower capacity. (When connecting more than 100%)
Do not exceed both of connectable cooling capacity range and maximum connectable indoor
unit quantity, otherwise it may cause hinder the return of the refrigerant oil and cause a com-
pressor breakdown.
1-1. Refrigerant system - (06-1) - 1. System design
SYSTEM
DESIGN
SYSTEM
DESIGN