2-23. Duct static pressure setting
¢ Mini duct type, Slim duct/Slim concealed floor type, Medium
static pressure duct type, and 72TLAV1 and 96TLAV in High
static pressure duct type
When the external static pressure is different from the normal static pressure, change the airflow set-
ting.
Setting of airflow can be changed by wireless remote controller, wired remote controller, and simple
remote controller.
How to set airflow (external static pressure):
• Wireless remote controller
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
– "Button name and function
" on page 07-16
– "Indoor unit (setting by wireless remote controller)" on page 07-78
– "Function details" on page 07-96
• Wired remote controller (UTY-RNKU)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
– "Button name and function" on page 07-27
– "Indoor unit (setting by UTY-RNKU)" on page 07-84
– "Function details" on page 07-96
• Simple remote controller (UTY-RSKU, UTY-RHKU)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
– "Button name and function" on page 07-39
– "Indoor unit (setting by UTY-RSKU, UTY-RHKU)" on page 07-90
– "Function details" on page 07-96
• Wired remote controller (Touch panel)
Airflow is set by function number 26 (static pressure).
For details, refer to the following sections:
– "Indoor unit (setting by UTY-RNRUZ)" on page 07-93
– "Function details" on page 07-96
CAUTION
• Setting of static pressure must be fall within the static pressure setting range described in "Fan
performance curve" in Chapter 4. INDOOR UNITS on page 04-141.
• Static pressure setting out of the static pressure setting range may cause product malfunction
such as capacity degradation or water leakage.
2-23. Duct static pressure setting - (07-128) - 2. Function settings