EasyManua.ls Logo

Fujitsu AIRSTAGE J-IIIL - Page 627

Fujitsu AIRSTAGE J-IIIL
904 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Button name and function
Address code or function indicator on the remote controller is as shown in the figures below.
For an outline of the address setting, refer to "Address setting" on page 07-3.
For the details of function number and setting number used for the function setting, refer to "Func-
tion details" on page 07-96.
It does not matter whether the refrigerant circuit address or indoor unit address is set first. (The
method shown here sets the indoor unit address first.)
During address setting mode, indoor unit reject the any operation command from remote con-
troller.
Function number
01: Indoor unit address
02: Refrigerant circuit address
Remote controller address
Remote controller address
setting number 00 to 15
SET BACK button
S
witches the remote controller
address setting number
SET TIME <” and “>button
S
witches the function number
Setting number
I
ndoor unit address valid range: 00 to 63
Refrigerant circuit address valid range: 00 to 99
SET TEMP. “Vand “Λ” button
S
witches the setting number
TIMER SET button
T
ransmits address/function setting
RELATED LINKS
"Indoor unit (setting by UTY-RNKU
)" on page 07-84
E
ntering setting mode
Hold down the 3 buttons of SET TEMP. “
“, SET TEMP. “ “, and FAN at the same time for 5 sec-
onds or longer. The setting mode will be activated.
Initial display of address setting mode
1-4. Address setting by remote controller - (07-27) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS

Table of Contents

Related product manuals