Indoor unit address setting
1. In the initial display of setting mode, by pressing the SET BACK button, select a remote con-
troller address. (Select the indoor unit you want to operate.)
Example: When remote controller address “01” is selected
R
emote controller address
2. Display the function number “01” by pressing the SET TIME “<” button or SET TIME “>” button.
3. Set up the indoor unit address by pressing the SET TEMP. “ ” or the SET TEMP. “ ” button.
(The setting range is from “00” to “63”.)
Example: When indoor unit address data “12” is set up
I
ndoor unit address data
4. Confirm the selected indoor unit address data by pressing the TIMER SET button. The data will
be transferred to the indoor unit.
• When the address data is properly set up on the indoor unit, the flashing of the number stops
and the set number will be displayed. (GOOD)
•
When the address data is not set up correctly, “- -” is displayed. (ERROR) Back to the previ-
ous step and set up the indoor unit address data again.
1-4. Address setting by remote controller - (07-28) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS