2-13. Central remote controller (UTY-DCGY)
¢ Address setting
1. Display the Installer Setting screen, and press the button to move the cursor to “Cen-
tral Controller Address Setting”.
Central Controller Address Setting
2. Press the button.
3.
Press the UP button or Down button.
4. Set the Address value. The Address value can be set from “00” to “15”.
5.
To complete the setting, press the
button.
NOTES:
Address No. can be set between “00” and “15”. (Up to 16 of this controller can be installed
in 1 system.)
When installing 2 or more controllers, set up so that Address No. does not overlap.
When installing multiple controllers in the same VRF network system, avoid to overlap the
Address No. of following controllers. (Even the same type of controllers, the Address No. is
not allowed to overlap.)
Touch panel controller, Central remote controller
Modbus convertor
Network convertor for LONWORKS, Network convertor for Group remote controller
For details, refer to the operating manual of the controller.
2-13. Central remote controller (UTY-DCGY) - (07-106) - 2. Function settings