3-7. BACnet gateway (Software: UTY-ABGXZ1)
• It is possible to connect medium to large sized BMS to VRF network system via BACnet, a global
standard for open networks.
•
A Maximum of 1,600 indoor units with 4 VRF network systems (a maximum of 400 indoor units
and 100 outdoor units for one network system) can be connected to one BACnet gateway.
• It is possible to control or monitor VRF network system from BMS via BACnet gateway.
• Compatible with BACnet (ANSI/ASHRAE-135-2012) application specific controller (B-ASC).
• Compatible with BACnet/IP over Ethernet.
• Scheduling function, alarm and event functions, electricity charge apportionment functions as well
as energy saving function are provided in BACnet gateway.
• Connection between VRF network system to personal computer is possible via small U10 USB
interface. However, both U10 USB interface and personal computer are locally purchased items.
¢ A
ccessory
Name and shape Q’ty Application
WHITE-USB-KEY
(Software protection key with software)
1
Includes the software and manuals of tool for BACnet
gateway
. Additionally, it works as the software protection
key.
Software protection key to be connected to an USB port on
the PC that the BACnet gateway is installed. BACnet
gateway runs only on a PC with this WHITE-USB-KEY.
¢ O
ther required devices (Locally purchased)
• To install tool for BACnet gateway, personal computer that satisfies the following system require-
ments is necessary.
Personal computer system requirement
Operating
system
• Microsoft Windows 7 Home Premium (32-bit or 64-bit) SP1
•
Microsoft Windows 7 Professional (32-bit or 64-bit) SP1
• Microsoft Windows 8.1 (32-bit or 64-bit)
• Microsoft Windows 8.1 Pro (32-bit or 64-bit)
• Microsoft Windows 10 Home (32-bit or 64-bit)
• Microsoft Windows 10 Pro (32-bit or 64-bit)
Supported languages: English, Chinese, French, German, Russian, Spanish, and Polish
CPU Intel Core i3 2 GHz or higher
Memory
• 2 GB or more (for Windows 7 [32-bit])
• 4 GB or more (for Windows 7 [64-bit], Windows 8.1, and Windows 10)
HDD 40 GB or more of free space
Display 1,024 × 768 or higher resolution
Interface
• Ethernet port (for getting access to the Internet using LAN) or Modem (for getting
access to the Internet using public telephone line)
• USB ports (Maximum of 5 ports) (Required only for the server PC that works as VRF
controller)
– Maximum of 1 USB ports are required for WHITE-USB-KEY connection
– Maximum of 4 USB ports are required for Echelon U10 USB Network Interface
NOTE: Maximum number of required USB ports depends on the applicable
system configuration.
Software Adobe Reader 9.0 or later
• Echelon U10 USB Network Interface – TP/FT-10 Channel (Model number: 75010R) (Required for
each VRF network)
3-7. BACnet gateway (Software: UTY-ABGXZ1) - (05-150) - 3. Adaptor/Convertor units