EasyManua.ls Logo

Fujitsu AIRSTAGE J-IIIL - Circular Flow Cassette Type

Fujitsu AIRSTAGE J-IIIL
904 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-2. Circular flow cassette type
Model name AUUB18TLAV2 AUUB24TLAV2 AUUB30TLAV2
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 18,000 24,000 30,000
kW 5.3 7.0 8.8
Heating
Btu/h 20,000 27,000 34,000
kW 5.9 7.9 10.0
Input power W 20 25 49
Fan
Airflow rate
HIGH
CFM (m
3
/h)
618 (1,050) 660 (1,120) 866 (1,470)
MED—HIGH 548 (930) 618 (1,050) 683 (1,160)
MED 530 (900) 548 (930) 630 (1,070)
MED—LOW 512 (870) 530 (900) 548 (930)
LOW 477 (810) 512 (870) 530 (900)
QUIET 459 (780) 459 (780) 459 (780)
Type × Q'ty Turbo × 1
Motor output W 81
Sound pressure level*
HIGH
dB (A)
33 35 40
MED—HIGH 32 33 36
MED 31 32 34
MED—LOW 30 31 32
LOW 29 30 31
QUIET 28 28 28
Heat exchanger type
Length in (mm) 87-7/16 (2,094)
Fin pitch FPI 21
Rows × Stages 2 × 10
Face area
ft
2
(m
2
)
4.7 (0.44)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net
in (mm)
9-11/16 × 33-1/16 × 33-1/16 (246 × 840 × 840)
Gross 11-3/4 × 37-13/16 × 37-3/8 (298 × 960 × 950)
Weight
Net
lb (kg)
53 (24) 54 (24.5)
Gross 64 (29) 65 (29.5)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35) Ø 3/8 (9.52)
Gas (Flare) Ø 1/2 (12.70) Ø 5/8 (15.88)
Drain hose I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
Cassette grille
(Option)
Model name UTG-LCGVCW
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
2-1/16 × 37-3/8 × 37-3/8 (53 × 950 × 950)
Gross 4-5/16 × 39-3/8 × 39-3/4 (110 × 1,000 × 1,010)
Weight
Net
lb (kg)
13 (6.0)
Gross 22 (10)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-2. Circular flow cassette type - (04-6) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS

Table of Contents

Related product manuals