1-3. Manual address setting method
¢ Address setting description
Refrigerant circuit address (Set A and Set D)
When there are 2 or more refrigerant systems in one VRF network system, an exclusive refrig-
erant circuit address should be set for each refrigerant system.
Refrigerant system: One refrigerant circuit which has connected between outdoor unit and in-
door unit by piping.
00 01 02 00 01 0201 01 010 1 2 02 02 020 1 2 00 01 0225 25 250 1 2
01 02 25
Refrigerant system 1 Refrigerant system 2 Refrigerant system 25
Setting example
Outdoor unit (Set A) Indoor unit (Set D)
Refrigerant circuit
address
Rotary switch setting Rotary switch setting
REF AD x10 REF AD x1 REF AD x10 REF AD x1
01
0 1 0 1
11
1 1 1 1
25
2 5 2 5
50
5 0 5 0
Setting range: 00—99 (Arbitrary numbers can be set.)
Same address should be set in all the indoor unit and outdoor unit in the same refrigerant
circuit.
1-3. Manual address setting method - (07-8) - 1. System settings