Setting subject Set Application Remarks
Outdoor unit
00
SetA
Set A Refrigerant circuit address Rotary switch REF AD x10, x1
Indoor unit
SetD SetE SetF
6
3 06 0
Set D Refrigerant circuit address
REF AD x10
REF AD x1
Set E Indoor unit address
IU AD x10
IU AD x1
Set F Remote controller address RC AD
Wired remote controller (2-wire) Set F Remote controller address Self: 0(Fixed)
Touch panel controller Set G Controller address Max. 16
Network convertor Set H Refrigerant circuit address For single split AC: Max. 100
Wired, simple remote controller
(3-wire)
Set J Dual remote control Switch 2 of DIP switch 1
Signal amplifier Set K Signal amplifier address
Network convertor for LonWorks Set M Convertor address
Central remote controller Set N Controller address Max. 16
Instructions for setting the address:
The refrigerant circuit address of the indoor units and outdoor units can be set to arbitrary
numbers in the range of 0 to 99.
The indoor unit address can be set to arbitrary numbers in the range of 0 to 63.
In case of 3-wire type of remote controller, set the remote controller address in the order of 0,
1, 2.....15. (Blank is not allowed.)
In the automatic address setting of 2-wire type remote controller, the remote controller ad-
dress is set to “0” automatically.
In the manual address setting of 2-wire type remote controller, the remote controller address
can be set to arbitrary numbers in the range of 1 to 15. (Setting to “0” is prohibited.)
Touch panel controller address can be set to arbitrary numbers in the range of 0 to 15.
The sum total of the Touch panel controller, Central remote controller, Network convertor for
Group remote controller, Modbus convertor, and Network convertor for LonWorks is a maxi-
mum of 16.
For Touch panel controller, Central remote controller, Network convertor for Group remote
controller, Modbus convertor, and Network convertor for LonWorks connected in same VRF
network system, set an exclusive address on each device.
1-2. Address setting - (07-7) - 1. System settings
FUNCTION
SETTINGS