1-3. Features of control system
¢ Simple wiring system
1 transmission line can interlink all equipments regardless refrigerant circuit.
Non polar 2-conductor transmission cable.
Central control equipment can be connected anywhere on the transmission line, with no need
to bring from the outdoor unit.
Making up the network system easily
Saving the total wiring length
Preventing incorrect connection
Saving installation time
¢ Adaption to large scale buildings
1 single VRF network can control an entire building using:
Total transmission wiring length can be extended up to 11,811 ft (3,600 m) with signal am-
plifier unit.
Up to 400 indoor units per group
Up to 100 outdoor units per group
Touch panel controller can be used for primary central control.
Multiple touch panel controllers may be sued to provide convenient control for multiple con-
vertor. (For details, refer to "Network convertor (UTY-VTGX)" on page 05-109.)
Can control Fujitsu mini-split and HFI models using a network convertor. (For details, refer
to "Network convertor (UTY-VTGX)" on page 05-109.)
System controller allows to control up to 4 VRF network systems (max. 1,600 indoor units),
suitable huge scale application.
¢ Reliability and easy maintenance
Stand-alone transmission network, allows each equipment to operate individually, thus failure
of the units does not affect other indoor units operation.
When a failure occurs, the error code is displayed on the individual controller and central con-
troller excepting wireless remote controller.
Also error histories can memorized by each individual controller and central controller except-
ing wireless remote controller.
System controller and Web monitoring tool allow to monitor operation status in real time via
Internet, and enable quick diagnoses.
Maintenance works is improved efficiency, because Service tool can be connected to any-
where on the transmission line.