2-21. Network convertor for LonWorks
¢ Switch location
SW3 SW4
JP1
SW7
SW2
SW1
D19
D9
D14
¢ Address setting
Following steps are necessary for setting address of
Network convertor.
For Touch panel controller, Central remote controller, Network convertor for Group remote con-
troller, Modbus convertor, and Network convertor for LonWorks connected in same VRF network
system, set an exclusive address on each device.
1. Turn on the power of the Network convertor.
2. Select the special mode by pressing and releasing SW7 (reset button) while holding down
SW4 (set button) until special mode “1” is displayed.
Special mode changes from “1” to “4” as shown in the following figure.
3. Press SW3 (mode button) to set special mode “2”. Special mode “2” is the address setting
mode.
4.
Press SW4 (set button). Current set address is displayed.
Example: Address no. 15 (Factory setting)
5. Press SW3 (mode button) to select the address. The displayed address changes as fol-
lows each time the mode button is pressed.
A00 A15A02A01
Example: Address no. 3 is selected.
6. Press SW4 (set button) to set the selected address.
Example: Address no. 3 is set
7. Turn the power off and on or press SW7 (reset button) to exit from address setting mode.
Anyone of the following indication will disappear:
: VRF Network address allocation is not registered by using Tool for Network convertor
: Binding and commissioning is not executed
: Normal mode (Ready for operation)
Others : Refer to the installation manual for more details.
2-21. Network convertor for LonWorks - (07-124) - 2. Function settings