3-4. Function summary of indoor unit external input and output
¢ Indoor unit external input function
Dry contact/ Apply voltage Dry contact DC 12 V Apply voltage
Function
Operation/Stop
(46-00)
(46-00)
Emergency stop
(46-01)
(46-01)
Forced stop
(46-02)
(46-02)
Forced thermostat off
(60-00)
(60-00)
Specifications
Terminal
CNA02
(Pin1-3)
CNA02
(Ch1: Pin1-3)
(Ch2: Pin2-3)
CNA04
(Pin1-2)
CNA01
(Pin1-2)
CNA01
(Ch1: Pin1-2)
(Ch2: Pin1-3)
CNA03
(Pin1-2)
Signal type Edge
Pulse *
Edge Edge
Pulse *
Edge
External
power
supply
Allowable
voltage
DC 12 to 24 V
Allowable
current
10 mA or less
Wire size
22 AWG (0.33 mm
2
), Twisted
Max. cable length 492 ft (150 m)
*: Default setting is Edge signal. If you use Pulse signal, DIP switch 2-2 must be set to “On”.
¢ I
ndoor unit external output function
Dry contact/ Apply voltage Dry contact
Function
Operation status
Error status
Indoor unit fan operation status
Auxiliary heater output ● *
Specifications
Terminal
CNB01
(Pin1-2)
CNB01
(Pin1-3)
CNB01
(Pin1-4)
CNB01
(Pin1-5)
Terminal output voltage DC 12 V
Wire size
22 AWG (0.33 mm
2
), Twisted
Max. cable length 82 ft (25 m)
*: Auxiliary heater is only available for duct type indoor unit. If you use Auxiliary heater output, DIP