2-11. Wall mounted type
Model name ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 4,000 7,500 9,500
kW 1.2 2.2 2.8
Heating
Btu/h 4,400 9,500 10,900
kW 1.3 2.8 3.2
Input power W 13 19 34
Fan
Airflow rate
HIGH
CFM (m
3
/h)
253 (430) 324 (550) 424 (720)
MED—HIGH 247 (420) 271 (460) 336 (570)
MED 230 (390) 247 (420) 294 (500)
MED—LOW 224 (380) 230 (390) 241 (410)
LOW 212 (360) 212 (360) 212 (360)
QUIET 194 (330) 194 (330) 194 (330)
Type × Q'ty Crossflow × 1
Motor output W 30
Sound pressure level*
HIGH
dB (A)
31 35 43
MED—HIGH 30 32 38
MED 28 30 34
MED—LOW 26 27 29
LOW 24 24 24
QUIET 22 22 22
Heat exchanger type
Length in (mm) 24-13/16 (630)
Fin pitch FPI 23
Rows × Stages 2 × 16
Face area
ft
2
(m
2
)
1.7 (0.16)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
10-5/16 × 32-5/16 × 8-1/8 (262 × 820 × 206)
Gross 10-3/8 × 34-1/4 × 12-15/16 (263 × 870 × 328)
Weight
Net
lb (kg)
17 (7.5)
Gross 22 (10)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35)
Gas (Flare) Ø 3/8 (9.52)
Drain hose I.D.: Ø 9/16 (13.8); O.D.: Ø 5/8 to 11/16 (15.8 to 16.7)
NOTES:
•
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-11. Wall mounted type - (04-20) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS