Model name ASUA12TLAV1 ASUA14TLAV1
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 12,000 14,000
kW 3.5 4.2
Heating
Btu/h 13,500 15,600
kW 4.0 4.6
Input power W 25 36
Fan
Airflow rate
HIGH
CFM (m
3
/h)
406 (690) 471 (800)
MED—HIGH 359 (610) 436 (740)
MED 330 (560) 400 (680)
MED—LOW 312 (530) 359 (610)
LOW 277 (470) 324 (550)
QUIET 194 (330) 194 (330)
Type × Q'ty Crossflow × 1
Motor output W 30
Sound pressure level*
HIGH
dB (A)
40 44
MED—HIGH 37 42
MED 35 40
MED—LOW 33 37
LOW 30 34
QUIET 24 24
Heat exchanger type
Length in (mm)
Main: 24-13/16 (630)
Sub: 24-13/16
(630)
Fin pitch FPI
Main: 23
Sub: 18
Rows × Stages
Main: 2 × 20
Sub: 1 × 4
Face area
ft
2
(m
2
)
2.2 (0.20)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
10-9/16 × 33-1/16 × 8 (268 × 840 × 203)
Gross 10-3/8 × 34-13/16 × 13-1/4 (270 × 884 × 336)
Weight
Net
lb (kg)
20 (9)
Gross 24 (11)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35)
Gas (Flare) Ø 1/2 (12.70)
Drain hose I.D.: Ø 9/16 (13.8); O.D.: Ø 5/8 to 11/16 (15.8 to 16.7)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.