2-4. Mini duct type
Model name ARUL4TLAV1
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 4,000
kW 1.2
Heating
Btu/h 4,400
kW 1.3
Input power W 26
Static pressure range inWG (Pa) 0 to 0.12 (0 to 30)
Standard static pressure inWG (Pa) 0.04 (10)
Fan
Airflow rate
HIGH
CFM (m
3
/h)
271 (460)
MED—HIGH 259 (440)
MED 247 (420)
MED—LOW 235 (400)
LOW 218 (370)
QUIET 200 (340)
Type × Q'ty Sirocco × 2
Motor output W 80
Sound pressure level*
HIGH
dB (A)
25
MED—HIGH 24
MED 23
MED—LOW 22
LOW 21
QUIET 20
Heat exchanger type
Length in (mm) 19-5/16 (490)
Fin pitch FPI 19
Rows × Stages 1 × 16
Face area
ft
2
(m
2
)
1.7 (0.16)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Fungicide type
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net
in (mm)
7-13/16 × 27-9/16 × 17-11/16 (198 × 700 × 450)
Gross 9-13/16 × 36-5/8 × 22-13/16 (250 × 930 × 580)
Weight
Net
lb (kg)
32 (14.5)
Gross 40 (18)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35)
Gas (Flare) Ø 3/8 (9.52)
Drain hose I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.