EasyManua.ls Logo

Fujitsu AIRSTAGE J-IIIL - Safety Devices; 10-1.Compact Cassette Type; 10-2.Circular Flow Cassette Type; 10-3.Cassette Type

Fujitsu AIRSTAGE J-IIIL
904 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. Safety devices
10-1. Compact cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUUA4TLAV2
250 V
3.15 A
280.4±27 °F
(138±15°C
)
Fan motor stop
221±36 °F
(105±20°C)
Fan motor restart
AUUA7TLAV2
AUUA9TLAV2
AUUA12TLAV2
AUUA14TLAV2
AUUA18TLAV2
AUUA24TLAV2
10-2. Circular flow cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUUB18TLAV2
250 V
3.15 A
257±18 °F
(125±10°C
)
Fan motor stop
248±18 °F
(120±10°C)
Fan motor restart
AUUB24TLAV2
AUUB30TLAV2
AUUB36TLAV2
AUUB48TLAV2
10-3. Cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUUB18TLAV
250 V
3.15 A
230
+27
-18
°F
(110
+15
-10
°C)
Fan motor stop
221
+27
-18
°F
(105
+15
-10
°C)
Fan motor Restart
AUUB24TLAV
AUUB30TLAV
AUUB36TLAV
10-4. Mini duct type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ARUL4TLAV1
250 V
3.15 A
275±27°F
(135±15°C
)
Fan motor stop
239±27°F
(115±15°C)
Fan motor Restart
10-1. Compact cassette type - (04-195) - 10. Safety devices
INDOOR
UNITS
INDOOR
UNITS

Table of Contents

Related product manuals