2-9. Floor/Ceiling type
Model name ABUA12TLAV2 ABUA14TLAV2 ABUA18TLAV2 ABUA24TLAV2
Power supply 1 phase ~ 208/230 V 60 Hz
Available voltage range 187—253 V
Capacity
Cooling
Btu/h 12,000 14,000 18,000 24,000
kW 3.5 4.1 5.3 7.0
Heating
Btu/h 13,500 15,600 20,000 27,000
kW 4.0 4.6 5.9 7.9
Input power W 30 42 74 99
Fan
Airflow rate
HIGH
CFM (m
3
/h)
389 (660) 459 (780) 589 (1,000) 589 (1,000)
MED—HIGH 365 (620) 436 (740) 536 (910) 548 (930)
MED 342 (580) 406 (690) 489 (830) 512 (870)
MED—LOW 324 (550) 377 (640) 442 (750) 471 (800)
LOW 306 (520) 353 (600) 389 (660) 436 (740)
QUIET 289 (490) 324 (550) 342 (580) 401 (680)
Type × Q'ty Sirocco × 2
Motor output W 80
Sound pressure level*
HIGH
dB (A)
36 40 46 47
MED—HIGH 34 39 44 45
MED 33 38 42 43
MED—LOW 31 36 40 41
LOW 29 35 37 39
QUIET 28 34 35 37
Heat exchanger type
Length in (mm) 31-1/2 (800)
Fin pitch FPI 21 19
Rows × Stages 2 × 12 3 × 12 4 × 12
Face area
ft
2
(m
2
)
2.3 (0.20)
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP monofilament net
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
in (mm)
7-13/16 × 39 × 25-13/16 (199 × 990 × 655)
Gross 12-5/8 × 45-1/4 × 31-1/8 (320 × 1,150 × 790)
Weight
Net
lb (kg)
55 (25) 57 (26) 60 (27)
Gross 77 (35) 79 (36) 84 (38)
Connection pipe diameter
Liquid (Flare)
in (mm)
Ø 1/4 (6.35) Ø 3/8 (9.52)
Gas (Flare) Ø 1/2 (12.70) Ø 5/8 (15.88)
Drain hose I.D.: Ø 3/4 (19.05); O.D.: Ø 1-1/16 (26.6)
NOTES:
•
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-9. Floor/Ceiling type - (04-18) - 2. Specifications
INDOOR
UNITS
INDOOR