2-2. Wiring specifications
Use an external input and output cable with appropriate external dimension, depending on the num-
ber of cables to be installed.
Cable type Cable size Max. cable length
Twisted pair cable
22 AWG (0.33 mm
2
)
492 ft (150 m)
CN131
(Yellow)
Input1 Input2 Input3 Input4 Input5
CN132
(Green)
CN133
(White)
CN134
(Red)
CN135
(Orange)
PCB
Connected
units
1 2 1 2 1 2 1 2 1 2
For each input, pin no.1 is of positive polarity and pin no.2 is of ground level.
2-3. External input
Setting to Low noise mode, Cooling priority/Heating priority selection, Outdoor unit operation peak
control, Batch/Emergency stop, and Electricity meter pulse are possible from the outside.
Connector Input signal Status
Outdoor
unit
CN131 (Yellow)
Off Normal operation
○
On Low noise mode operation
CN132 (Green) *
1
Off Cooling priority
○
On Heating priority
CN133 (White)
Off Normal operation
○
On Outdoor unit operation peak control
CN134 (Red)
Off Normal operation
○
On
Batch stop or Emergency stop operation *
2,
*
3
CN135 (Orange) *
4
No pulse No information from electricity meter
○
Pulse Power usage information from electricity meter
*
1
:
The external input priority mode must be set by pressing push button on outdoor unit PCB.
*
2
:
Batch stop or Emergency stop pattern can be selected by pressing push button on outdoor
unit PCB.
*
3
:
The emergency stop function mounted in the equipment does not guarantee the regula-
tions of each country. For this reason, sufficient checking is necessary regarding use. Es-
pecially, since the fact that the equipment may not be emergency-stopped in the case of
breaking of the wiring to the external input terminals and communication line, communica-
tion error due to noise, VRF external input circuit trouble, etc. must be considered, the pro-
vision of double measures that add direct interruption of the power supply by switch, etc. is
recommended as a precaution.
*
4
:
The width of Pulse input signal to CN135 must be 50 ms or more, and the interval of the
signal must be 50
ms or more.