4-3. Central remote controller (UTY-DCGYZ1)
External input and output functions and related components are as follows:
External input External output Input select Connector
External connect kit
(Optional parts)
Control input
Dry contact CN12, CN13 UTY-XWZXZ7
Apply voltage CN14, CN15 UTY-XWZXZ8
Operation status
CN18 UTY-XWZXZA
Error status
RELATED LINKS
"External input
" on page 08-69
"External output" on page 08-73
"Optional parts" on page 08-74
"Function summary of controller external input/output" on page 08-75
¢ E
xternal input
This function performs “Emergency stop” or “All On / All Off” by using the signal to be input externally
at external input terminals.
I
nput select
Use either one of Apply voltage terminal or Dry contact terminal according to the application. (Both
types of terminals cannot be used simultaneously.)
CN12 (CH1) and CN13 (CH2): Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry contact
terminal CN12 (Ch1) and CN13 (Ch2).
PCB
CN13 (Ch2, Black)
CN12 (Ch1, White)
*
Connected unit
*: Short circuit detection resistance (R
ON
): ≤ 500 Ω
Open circuit detection resistance (R
OFF
): ≥ 100 kΩ
A twisted pair cable 22 AWG (0.33 mm
2
) should be used. (Maximum cable length:
82 ft [25 m])
Input method Terminal Input signal Operation
Edge CN12 (Ch1)
Low → High
“Emergency Stop”
or “All on”
High → Low
“Emergency Stop” reset
or “All Off”
Pulse
CN12 (Ch1) Low → High
“Emergency Stop”
or “All on”
CN13 (Ch2) Low → High
“Emergency Stop” reset
or “All Off”
4-3. Central remote controller (UTY-DCGYZ1) - (08-69) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT