10-9. Floor/Ceiling type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ABUA12TLAV2
250 V
3.15 A
275±27°F
(135±15°C
)
Fan motor stop
239±27°F
(115±15°C)
Fan motor restart
ABUA14TLAV2
ABUA18TLAV2
ABUA24TLAV2
10-10. Ceiling type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ABUA30TLAV2
250 V
5 A
275±27°F
(135±15°C
)
Fan motor stop
239±27°F
(115±15°C)
Fan motor restart
▲*
ABUA36TLAV2
*: Including in Drain pump unit (Optional parts)
10-11. Wall mounted type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ASUA4TLAV1
250 V
3.15 A
221±18°F
(105±10°C
)
Fan motor stop
194±18°F
(90±10°C)
Fan motor restart
ASUA7TLAV1
ASUA9TLAV1
ASUA12TLAV1
ASUA14TLAV1
ASUB18TLAV1 302±27°F
(150±15°C)
Fan motor stop
248±27°F
(120±15°C)
Fan motor stop
Active at
215.6°F
(102°C)
ASUB24TLAV1
ASUA30TLAV2 302±27°F
(150±15°C)
Fan motor stop
Less than
275°F (135°C)
Fan motor restart
ASUA36TLAV2
ASUA7TLAV 212±27°F
(100±15°C)
Fan motor stop
185±18°F
(85±10°C)
Fan motor stop
Active at
215.6°F
(102°C)
ASUA12TLAV
ASUB18TLAV 302±27°F
(150±15°C)
Fan motor stop
248±27°F
(120±15°C)
Fan motor stop
ASUB24TLAV