¢ Installation space
Unit: in (mm)
40 (1,000)
or
more
40 (1,000)
or more
71 (1,800) to
11 (262)
or more
Strong and durable ceiling
Obstruction
Floor
H
Be sure to make function setting with the remote controller according to the installed ceiling height.
H: The maximum height from floor to ceiling
Ceiling height
Model name
AUUA4 AUUA7 AUUA9 AUUA12 AUUA14 AUUA18 AUUA24
Standard 106 (2,700)
High ceiling 118 (3,000)
I
nstallation notices
When installing the indoor unit, be careful about the maintenance space.
To set “3-direction”, Air outlet shutter plate (option) must be installed, and the “outlet-direction”
need to be switched to “3-way” by the remote controller.
4 (100) or more
4 directions
3 directions
Piping position
In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited. (Ceil-
ing height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)
Use the Insulation kit for high humidity (option), when the condition under the roof is over 80% in
humidity and over 86°F (30°C) in temperature. Otherwise, there is a risk of condensation on the
ceiling.
4-1. Compact cassette type - (04-29) - 4. Dimensions
INDOOR
UNITS
INDOOR
UNITS