¢ Dimensions
Unit: in (mm)
For M4 × 16 mm
screws
Ho
l
e pitch
3-Ø3/16 (4.5)
3-7/8 (98)
2-Ø3/8 (10)
4-3/4 (121)
3/8 (10)
1-11/16 (43)
Hole: 1/16 x 5/16 (2 x 8)
4
-5/8 (117)
5-1/2 (140)
For open case
1-3/161
(30)
1-3/16
(25)
1
For code (> Ø1/4 (7))
Hole: 2-Ø1/4 (7)
For code (≤ Ø1/4 (7))
2-Ø5/16 (8)
For code (> Ø3/16 (5))
Hole: 2-Ø3/16 (5)
For code (≤ Ø3/16 (5))
(25) (30)
¢ S
pecifications
Input power W 2
Temperature
Operating °F (°C) 32 to 114.8 (0 to 46)
Packaged °F (°C) 14 to 140 (-10 to 60)
Humidity Packaged %
0 to 95 (RH)
No condensation
Dimensions (H × W × D) in (mm) 5-1/2 × 4-5/8 × 1-11/16 (140 × 117 × 43)
Weight oz (g) 9 (250)
W
iring specifications
Use Cable size Wire type Remarks
Transmission cable
22 AWG
(0.33
mm
2
)
LEVEL 4 (NEMA)
Non-polar 2 core, twisted pair
solid core shielded
LonWorks compatible cable
Remote controller
cable
(2-wire type)
22 to 16 AWG
(0.33 to 1.25 mm
2
)
Non-polar 2 core
Use sheathed PVC cable or
shielded cable in accordance
with the regional cable standard.
Remote controller
cable
(3-wire type)
22 AWG
(0.33 mm
2
)
Polar 3 core
3-1. Network convertor (UTY-VTGX) - (05-114) - 3. Adaptor/Convertor units