EasyManua.ls Logo

Fujitsu AIRSTAGE J-IIIL - Page 457

Fujitsu AIRSTAGE J-IIIL
904 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¢ Functions
Start/Stop Timer setting
Temperature control Fan control
Operation mode
Central control
(Lock the remote controller functions)
¢ D
imensions
Unit: in (mm)
For dust proof bushing
Ø1-1/8 (28)
3-1/2 (89.5) 3-1/2 (89.5)
For dust proof bushing
Ø1-1/8 (28)
1-1/8 (29)
2-Ø3/16 (5)
For M4 × 20 mm
screws
Hole pitch
3-3/4 (95)
Hole pitch
3-3/4 (95)
8-5/16 (211)
2-5/8 (67)
4-Ø3/16 (5)
For M4 × 20 mm screws
Ø7/8 (22) For conduit
9-1/2 (241.6)
10-11/16 (272) Hole pitch
11-5/16 (288)
¢ S
pecifications
Power supply V 1 Ø AC 208—240
Power source frequency Hz 50/60
Input power W 3.0
Temperature
Operating °F (°C) 32 to 114.8 (0 to 46)
Packaged °F (°C) 14 to 140 (-10 to 60)
Humidity Packaged %
0 to 95 (RH)
No condensation
Dimensions (H × W × D) in (mm) 2-5/8 × 11-5/16 × 8-5/16 (67 × 288 × 211)
Weight lb (g) 3 (1,500)
Fuse capacity A 3
W
iring specifications
Use Cable size Wire type Remarks
Power supply cable
(using remote
control cable)
20 to 16 AWG
(0.5 to 1.25 mm
2
)
60245 IEC 57 or equivalent
1 Ø AC 208—240 V 50/60 Hz,
2 wire + ground (Always ground
the unit)
Transmission cable
22 AWG
(0.33 mm
2
)
LEVEL 4 (NEMA)
Non-polar 2 core, twisted pair
solid core shielded
LonWorks compatible cable
Remote controller
cable
22 AWG
(0.33 mm
2
)
Polar 3 core
Use sheathed PVC cable or
shielded cable in accordance
with the regional cable standard.
External input/
output cable
22 AWG
(0.33 mm
2
)
Polar 2 core, twisted pair
Use shielded cable in
accordance with the regional
cable standard.
3-2. Network convertor (UTY-VGGXZ1) - (05-119) - 3. Adaptor/Convertor units