¢ Setting up each indoor unit
Setting must be performed on each indoor unit by repeating following procedures.
"Preparation" on page 07-84
"Indoor unit function setting" on page 07-84
"Completion of setting mode" on page 07-30
0001 0101 0201 1301 1401 15010 1 2 0 1 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Wired remote
controller
W
ired remote
controller
Wired remote
controller
¢
Resetting the power after setting up all indoor units
NOTES:
If the reset is not performed, function cannot be read correctly.
After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
After the 2 minutes has passed, power can be restored.
The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
2-5. Indoor unit (setting by UTY-RNKU) - (07-86) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS