¢ DIP switch setting
• SET2-1: Terminal resistance setting
When there is no other terminal resistance in the network segment to which the convertor is
connected, set to “ON”.
SET2-1 Terminal resistance Factory setting
ON Enable
OFF Disable ♦
• SET2-2: Setting prohibited
SW1 Factory setting
OFF Fixed at OFF ♦
ON Setting prohibited
• SET2-3: Setting prohibited
SW1 Factory setting
OFF Fixed at OFF ♦
ON Setting prohibited
• SET2-4: Used remote controller setting
Change the DIP switch setting depending on the remote controller model name attached to
the indoor unit.
NOTE: When 2-wire type remote controller is connected, set to “OFF” for all models.
SET2-4 Factory setting
ON
Wireless remote controller model name:
AR-RAK1E
3-wire type wired remote controller model name:
AR-WAG1E (UTY-RNNGU)
YYYYYYYY
Model name
Rear view
OFF Other than the remote controller mentioned above ♦
• SET3: Remote controller 2-wire/3-wire switching
Set this setting so that the configuration match with the setting of the used indoor unit.
Also, set matched with the connection method of the remote controller cable to be connected.
SET3 RC 2-wire/3-wire Factory setting
2WIRE 2-wire type ♦
3WIRE 3-wire type
2-17. Network convertor (UTY-VTGX) - (07-116) - 2. Function settings